2010-02-03 16:29:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 4. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR
 EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009.
  
  