Plan Review Notes For Permit 10010306 |
Permit Number |
10010306 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-27 16:46:51 | DENIED | | REFERENCE: | | FBC-2007 PLUMBING | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. SHTS P1 & P2. THE TITLE BLOCKS FOR THE ENGINEER | | SHALL LEGIBLY INDICATE THE NAME AND LICENSE NUMBER OF | | THE ENGINEER AS WELL AS THE CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON | | EACH SHEET. FAC 61G15-23.002(2) & FS 471.025. (THE CA# | | EB-000306 IS NOT ON FILE). | | | | 2. SHT P1 A TRAP IS REQUIRED ON THE SANITARY DRAIN FOR | | THE TRENCH DRAIN. SECTION 1002.1. PLEASE INDICATE IF | | THERE IS MORE THAN ONE DRAIN AS THIS IS NOT SHOWN ON | | THE RISER DIAGRAM. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|