Plan Review Notes
Plan Review Notes For Permit 10010306
Permit Number 10010306
Review Stop P
Sequence Number 1
Notes
Date Text
2010-01-27 16:46:51DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1 & P2. THE TITLE BLOCKS FOR THE ENGINEER
 SHALL LEGIBLY INDICATE THE NAME AND LICENSE NUMBER OF
 THE ENGINEER AS WELL AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. FAC 61G15-23.002(2) & FS 471.025. (THE CA#
 EB-000306 IS NOT ON FILE).
  
 2. SHT P1 A TRAP IS REQUIRED ON THE SANITARY DRAIN FOR
 THE TRENCH DRAIN. SECTION 1002.1. PLEASE INDICATE IF
 THERE IS MORE THAN ONE DRAIN AS THIS IS NOT SHOWN ON
 THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  