2010-02-08 10:02:27 | *DENIED* |
| |
| |
| 1) NOTE: PLEASE EXPLAIN THE SUBMITTAL OF METHOD B WHICH |
| BE FOR PRESCRIPTIVE FOR SPACE BY SPACE OR SHELL |
| BUILDINGS. WHEN USING METHOD B ALL SPACES INCLUDING |
| EXTERIOR WOULD REQUIRE ALLOWANCES PER 13-415.AB.5, |
| 13-415.AB.2.2 FOR EACH SPECIFIC SPACE/AREA. IT IS NOT |
| PERMISSIBLE TO USE ONE FORM *B* FOR ALL |
| ROOMS/SPACES/AREAS. |
| PLEASE SEE METHOD *A* WHEN APPLYING WHOLE BUILDING. |
| LIGHTING POWER DENSITIES CAN NOT BE CONFIRMED WITHOUT A |
| SPECIFIC FIXTURE LEGEND. |
| |
| 2) NOTE: TITLE BLOCKS TO BE COMPLETE ON PLANS FOR ALL |
| INFORMATION AS REQUIRED UNDER FAC 61G15-23.002. |
| |
| 3) NOTE: EXTERIOR LIGHTING IS SHOWN ON A SP SWITCH |
| HOWEVER ALSO MENTIONS SOME SORT OF TIMER. PLEASE SEE |
| FBC 13-415.AB.1.4. |
| MUST BE ONE OF THE TWO FOLLOWING TYPE OF CONTROLS OR |
| BOTH. PHOTO-SENSOR TYPE OR ASTRONOMICAL TIME CLOCK WITH |
| MINIMUM REQUIRED 10HR BACK UP FOR PROGRAMMING. |
| |
| 4) NOTE: ALL CONTINUOUS LOADS ARE REQUIRED TO BE SHOWN |
| AT 125%. |
| 215.3,230.42 |
| |
| 5) NOTE: PLEASE SHOW REQUIRED GROUNDING ELECTRODE |
| SYSTEM AT THE DETACHED BUILDING PER 250.32, 250.50 |
| |
| 6) NOTE: PLEASE VERIFY THE NAMEPLATE RATING OF THE AHU |
| AND THE REQUIRED MINIMUM SIZING. PLEASE SEE MINIMUM |
| OVER CURRENT PROTECTION FOR AHU PER NEC 424.3. ( 125% ) |
| |
| 7) NOTE: PLEASE SEE 225.31-225.39 AS A DISCONNECTING |
| MEANS IS REQUIRED AT DETACHED BUILDING. THE PANEL IS |
| SHOWN AS A 100AMP MLO WHICH IS NOT ACCEPTABLE. |
| |
| 8) NOTE: PLEASE SEE 440.11 AND 440.12 FOR MISSING AHU |
| DISCONNECT. |
| |
| |
| |
| |