2010-02-01 16:35:38 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. PLANS PREPARED BY A LICENSED DESIGN PROFESSIONAL, |
| (LANDSCAPE ARCHITECT), SHALL BE SIGNED, SEALED AND |
| DATED BY THE DESIGN PROFESSIONAL. SECTION 106.1, FAC |
| 61G1.10 & FS 481.321. PLANS SUBMITTED ARE COPIES OF |
| SIGNED/SEALED/DATED PLANS. |
| |
| 2. SHT 2 0F 2 SHOW THE LOCATION OF THE METER, THE |
| BACKFLOW, THE CONTROLLER AND THE RAIN SENSOR ON THE |
| PLANS. SECTION 106.1.1. |
| |
| 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED. SECTION |
| 105.1. |
| |
| 4. A SEPARATE BACKFLOW PERMIT IS REQUIRED. BACKFLOW |
| SHALL BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR. |
| FS 489.105(M) & SECTION 608.13.2/608.13.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |