2010-01-27 14:51:06 
 ** PROVISO *
  
 ** THE FOLLOWING ITEMS LISTED BELOW ARE REQUIRED TO BE
 REVISED, SUBMITTED FOR REVIEW AND ON-SITE FOR INSPECTOR
 BEFORE FINAL ELECTRICAL INSPECTION. ALL OTHER REVISIONS
 ARE REQUIRED BEFORE ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: THE PANEL SCHEDULE CONTAINS SEVERAL CIRCUITS
 WHICH ARE LISTED A *EXISTING POWER* HOWEVER NOT
 INFORMATION ON PLANS OR WHAT THESE FEED IS PROVIDED.
 THERE ARE SEVERAL SINGLE POLE CIRCUITS AS WELL AND A
 2-POLE CIRCUIT WHICH IS NOT SHOWN. ALL CIRCUITING IS TO
 BE SHOWN ON PLANS AND IDENTIFIED ON PANEL SCHEDULE.
 CIRCUITING FROM THIS TENANT SPACE PANEL MAY NOT FEED
 OTHER TENANT SPACES OR COMMON AREAS.
 PLEASE ALSO BE SURE TO UPDATE THE ROOF TOP GFI
 RECEPTACLES WHICH ARE NOTED ON PLANS.
 408.4.
  
 2) NOTE: THE WATER HEATER IN THE LOAD CALCULATIONS
 NOTES A DE-RATING OF 65%. THE ACTUAL CALCULATIONS DO
 DEPICT THE REQUIRED 125% PER 422.13. A CALL WAS PLACED
 TO DESIGN TEAM AND APPEARS TO BE A MISPRINT. PLEASE
 ADJUST WHEN REVISING FINAL SET OF PLANS.
  
 3) NOTE: SHEET E3.01 NOTES CONTAIN CODE REFERENCES.
 MOST ARE OK HOWEVER PLANS CONTAIN REFERENCE TO THE 2005
 NFPA-72. THE STATE HAS NOT YET ADOPTED THE 2005 EDITION
 OF NFPA-72.
 THIS WAS REDLINED ON BOTH SETS. PLEASE ADJUST WHEN
 MAKING OTHER CHANGES TO THE PLANS.
  
 4) NOTE: AS NOTED AND STAMPED ON PLANS, ALL LOW VOLTAGE
 IS REQUIRED TO BE UNDER SEPARATE PERMITS. MAIN PLANS
 MAY BE REFERENCED FOR PHONE AND DATA TURN AROUND
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  