2010-01-20 14:50:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. PER TABLE 403.1 A TOILET ROOM AND A DRINKING
 FOUNTAIN ARE REQUIRED.
  
 2. PER SECTION 11-4.1.3 THE PROVIDED TOILET ROOM SHALL
 BE ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING THE
 LOCATION OF THE ACCESSIBLE TOILET ROOM AND COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, & 11-4.22 WITH ALL
 SUBSECTIONS.
  
 3. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  