Plan Review Notes For Permit 10010259 |
Permit Number |
10010259 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-02-09 11:52:52 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET. | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | EDITION. | | | | ATTENTION: THE SCOPE OF WORK SHALL BE REVIEWED AS A NEW | | BUSINESS OCCUPANCY (CHAPTER 38 OF NFPA 101) | | | | 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALLL BE | | REFERENCED. | | | | 4. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF | | THE SPACE. | | | | 5. IT APPEARS THAT THERE WILL BE A SINGLE EXIT ONLY, | | SHOW THAT THE TOTAL DISTANCE FROM ANY POINT SHALL NOT | | EXCEED 100 FEET. | | | | 6. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS | | IN TERMS OF CLASS A, CLASAS B, OR CLASS C. SPECIFY | | INTERIOR FLOOR FIONISH IN TERMS OF CLASS I OR CLASS II. | | | | 7. SHOW LOCATION OF THE 2A10:BC RATED PROTABLE FIRE | | EXTINGUISHER IN THE BUSINESS OCCUPANCY. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | |
|