Plan Review Notes
Plan Review Notes For Permit 10010259
Permit Number 10010259
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-01 15:34:42 
 ** DENIED REVIEW *
  
 1) NOTE: NO DESIGN CODES ON PLANS FOR PERMIT
 APPLICATION MADE AFTER OCTOBER 1ST, 2009.
 SHOULD HAVE THE FOLLOWING AT A MINIMUM.
 2008 NFPA-70
 2006 NFPA-101
  
 2) NOTE: MIXED USE OCCUPANCY CLASSIFICATION UNDER FBC
 CHAPTER 3. THIS IS A COMMERCIAL OFFICE SPACE.
 PLEASE SEE FBC CHAPTER 13, 13-415.AB.5 FOR LIGHTING
 PERFORMANCE CALCULATIONS. THE SUBMITTED FORM FOR
 RESIDENTIAL USE IS NOT ACCEPTABLE. THE PERSON PREPARING
 DOCUMENTS MUST HAVE AN ORIGINAL SIGNATURE. THE
 SUBMITTED FORM IS NOT ORIGINAL SIGNATURE.
 FBC 13-103.1
  
 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR OCCUPANCY AND ADJUST PER NEC
 220.12,220.14,220.42 ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 215.3, 230.42
  
 4) NOTE: PLEASE SEE NEC AND FBC FOR *TEMPORARY USE* AND
 TIME LIMITATIONS.
 RE-PLAT HOLD STILL ON SYSTEM TO BE ADDRESSED BEFORE USE
 PROPOSED. NEEDS TO BE A FEE SIMPLE TOWN-HOUSE. THIS IS
 NOT A MULTI-FAMILY BUILDING OR CONDO.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  