2010-01-27 09:02:18 | 2007 FBC W/2007 REVISIONS |
| SALES OFFICE |
| |
| DENIED BY BUILDING |
| |
| 1) THE GARAGE IS REQUIRED TO BE CONVERTED BACK TO THE |
| ORIGINAL CONDITION WHEN THE TIME ALLOTED BY ZONING FOR |
| THE TEMPORARY SALES OFFICE HAS EXPIRED. |
| |
| 2) SPECIFY THE APPLICABLE CODE INFORMATION ON THE |
| PLANS. |
| |
| 3) SPECIFY THE WIND DESIGN DATA ON THE PLANS AS |
| REQUIRED BY FBC 1603.1. SPECIFY THE BASIC WINDSPEED, |
| IMPORTANCE FACTOR, EXPOSURE, COMPONENT AND CLADDING |
| PRESSURES, ETC. |
| |
| 4) SPECIFY THE HURRICANE STRAPS AND CONNECTORS THAT |
| WILL BE USED ON THE EXTERIOR WOOD FRAME IN-FILL WALL AT |
| THE GARAGE DOOR OPENING AND SUBMIT 2 COPIES OF PRODUCT |
| APPROVALS FOR THEM AS REQUIRED BY DCA RULE 9B-72. |
| |
| 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE |
| 9B-72. |
| |
| 6) ELEVATION NOTE #2 ON SO-1 REFERENCE FBC |
| 2510.5.1/2517.5.11. ACCORDING TO THE 2007 FBC THE FIRST |
| SECTION IS NOT RELEVANT AND THE SECOND DOES NOT EXIST. |
| PLEASE CORRECT. |
| |
| 7) THE SALES OFFICE IS REQUIRED TO BE EQUIPPED WITH A |
| TOILET FACILITIES PER 2007 FBC PLUMBING SECTIONS 403.1, |
| 403.2 AND 403.4. THE PLANS SHOW THAT THE DOOR FROM THE |
| GARAGE (SALES OFFICE) TO THE DWELLING UNIT IS TO BE |
| BLOCKED OFF. IF THE SALES OFFICE AREA IS SEPARATED FROM |
| THE DWELLING UNIT, THEN A TOILET FACILITY IS REQUIRED |
| IN THE SALES OFFICE. IN ORDER FOR THE TOILET ROOM IN |
| THE DWELLING UNIT TO BE USED THE DOOR CAN NOT BE |
| BLOCKED AND BECAUSE FBC 11-4.1.1(4) REQUIRES TEMPORARY |
| STRUCTURES TO COMPLY WITH ACCESSIBILITY, THE TOILET |
| ROOM IS REQUIRED TO BE ON AN ACCESSIBLE ROUTE PER |
| 11-4.1.3 (11). |
| |
| 8) SUBMIT TWO COPIES OF A SITE PLAN WITH DETAILS |
| SHOWING COMPLIANCE WITH FBC 11-4.1.2 (5) AND 11-4.6 FOR |
| ACCESSIBLE PARKING REQUIREMENTS AND ACCESSIBLE ROUTES. |
| |
| 9) THE DOORS IN THE OFFICE AREA ARE REQUIRED TO COMPLY |
| WITH FBC 11-4.13.6 FOR MANEUVERING CLEARANCES AND |
| 11-4.13.9 FOR HARDWARE. |
| |
| 10) PROVIDE DETAILS OF PROPOSED DROPPED CEILING IN |
| OFFICE AREA. SPECIFY HEIGHT, MATERIALS, AND STRUCTURAL |
| DETAILS. |
| |
| PLEASE RESPOND TO REVIEW COMMENTS IN WRITING. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |