Plan Review Notes For Permit 10010182 |
Permit Number |
10010182 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-24 16:42:26 | BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE REVISION | | FOR APPROVAL PRIOR TO CONSTRUCTION TO AVOID CONFLICTS | | OR DELAYS). | | | | 1- AREA BY THE DOOR LEADING TO THE WOMEN'S VESTIBULE | | NEED TO COMPLY WITH THE DIMENSIONS SHOWN ON FIGURE | | 25(A) OF CHAPTER 11 OF 2007 FBC FOR FRONT APPROACH. SEE | | COPY OF FIGURE 25(A) ATTACHED ON DRAWING A-101. | | ***NOTE: REVISION #1 SHOWN ON SHEET A-101 IS NOT DRAWN | | TO SCALE. 2'-6" DOOR DOESN'T COMPLY. REVISE AS REQUIRED | | TO COMPLY WITH FIGURE 25(A). | | | | 2- DOOR FOR THE UTILITY CLOSET NEED TO COMPLY WITH SEC. | | 11-4.13.5 FBC 2007. 2'-8" DOOR DOESN'T PROVIDE 32" | | CLEAR OPENING. |
|