Plan Review Notes For Permit 10010182 |
Permit Number |
10010182 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-28 16:58:43 | BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- AREA BY THE DOOR LEADING TO THE WOMEN'S VESTIBULE | | DOESN'T COMPLY WITH THE MANEUVERING CLEARANCES AT | | DOORS. SEC. 11-4.13.6 FBC 2007. IT DOESN'T HAVE THE | | DIMENSIONS REQUIRED ON FIGURE 25(A) FOR FRONT APPROACH. | | | | 2- DOOR FOR THE UTILITY CLOSET DOESN'T COMPLY WITH THE | | MINIMUM DOOR SIZE REQUIRED BY SEC. 11-4.13.5 FBC 2007. | | NOTE: THIS UTILITY CLOSET DOESN'T MEET THE EXCEPTION, | | THEREFORE 32" CLEAR OPENING IS REQUIRED. | | | | 3- SHEET A-100: REVISE THE CODE SUMMARY INFORMATION. | | THE CURRENT CODE IN EFFECT IS THE 2007 FBC WITH 2009 | | REVISIONS. NOT 2004 FBC. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. | | | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|