Plan Review Notes
Plan Review Notes For Permit 10010182
Permit Number 10010182
Review Stop B
Sequence Number 1
Notes
Date Text
2010-01-28 16:58:43BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- AREA BY THE DOOR LEADING TO THE WOMEN'S VESTIBULE
 DOESN'T COMPLY WITH THE MANEUVERING CLEARANCES AT
 DOORS. SEC. 11-4.13.6 FBC 2007. IT DOESN'T HAVE THE
 DIMENSIONS REQUIRED ON FIGURE 25(A) FOR FRONT APPROACH.
  
 2- DOOR FOR THE UTILITY CLOSET DOESN'T COMPLY WITH THE
 MINIMUM DOOR SIZE REQUIRED BY SEC. 11-4.13.5 FBC 2007.
 NOTE: THIS UTILITY CLOSET DOESN'T MEET THE EXCEPTION,
 THEREFORE 32" CLEAR OPENING IS REQUIRED.
  
 3- SHEET A-100: REVISE THE CODE SUMMARY INFORMATION.
 THE CURRENT CODE IN EFFECT IS THE 2007 FBC WITH 2009
 REVISIONS. NOT 2004 FBC.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712