Plan Review Notes
Plan Review Notes For Permit 10010169
Permit Number 10010169
Review Stop B
Sequence Number 1
Notes
Date Text
2010-01-12 08:59:17RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE. THERE ARE TWO DIFFERENT APPR0VED
 ASSEMBLIES SUBMITTED.
  
 2- CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION
 IS GOING TO BE USED ON SELECTED APPROVED ASSEMBLY TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
  
 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 09-0224.01 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO HAVE INTO CONSIDERATION THAT ACCORDING
 TO THE 2009 REVISIONS THIS BUILDING IS LOCATED IN
 EXPOSURE "C" NOT "B".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712