Plan Review Notes For Permit 10010151 |
Permit Number |
10010151 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2010-04-01 10:28:36 | 2007 FBC W/2009 REVISIONS | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) PORTIONS OF THE SIGNED AND SEALED PLANS ARE IN | | PENCIL WHICH CAN BE ALTERED. THE FAC CHAPTER | | 61G15-23.002 (3) SPECIFIES THAT A PROFESSIONAL ENGINEER | | SHOULD NOT SEAL DOCUMENTS WHICH CAN BE CHANGED. PLEASE | | CORRECT. | | | | 2) SUBMIT TWO SETS OF PLANS THAT HAVE BEEN DRAWN TO A | | MINIMUM 1/8 INCH SCALE. FBC 106.1.3 CITY AMENDMENTS. | | | | 3) SPECIFY THE LEVEL OF ALTERATION AND THE BUILDING | | CODE EDITION IN EFFECT ON THE PLANS. ( LEVEL 2 | | ALTERATION/ 2007 FBC W/2009 REVISIONS) | | | | 4) THE OCCUPANCY TYPE FOR A NAIL SALON WOULD BE GROUP B | | PER FBC 302. SPECIFY ON THE PLANS. | | | | 5) THE OCCUPANT LOAD IS BASED ON THE FLOOR AREA OF THE | | BUSINESS, WHICH IS 100 SQFT PER OCCUPANT OF THE GROSS | | AREA OF THE SPACE. SPECIFY THE TOTAL SQFT OF THE SPACE | | AND THE OCCUPANT LOAD ON THE PLANS. SEE FBC TABLE | | 1004.1.1 | | | | 6) PROVIDE SIGNED AND SEALED STRUCTURAL DETAIL DRAWINGS | | OF THE TWO NEW RECESSED CEILING AREAS SHOWING ALL | | MATERIALS AND CONNECTIONS. SEE FBC 1603 AND 1604. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|