Plan Review Notes
Plan Review Notes For Permit 10010151
Permit Number 10010151
Review Stop B
Sequence Number 3
Notes
Date Text
2010-04-01 10:28:362007 FBC W/2009 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) PORTIONS OF THE SIGNED AND SEALED PLANS ARE IN
 PENCIL WHICH CAN BE ALTERED. THE FAC CHAPTER
 61G15-23.002 (3) SPECIFIES THAT A PROFESSIONAL ENGINEER
 SHOULD NOT SEAL DOCUMENTS WHICH CAN BE CHANGED. PLEASE
 CORRECT.
  
 2) SUBMIT TWO SETS OF PLANS THAT HAVE BEEN DRAWN TO A
 MINIMUM 1/8 INCH SCALE. FBC 106.1.3 CITY AMENDMENTS.
  
 3) SPECIFY THE LEVEL OF ALTERATION AND THE BUILDING
 CODE EDITION IN EFFECT ON THE PLANS. ( LEVEL 2
 ALTERATION/ 2007 FBC W/2009 REVISIONS)
  
 4) THE OCCUPANCY TYPE FOR A NAIL SALON WOULD BE GROUP B
 PER FBC 302. SPECIFY ON THE PLANS.
  
 5) THE OCCUPANT LOAD IS BASED ON THE FLOOR AREA OF THE
 BUSINESS, WHICH IS 100 SQFT PER OCCUPANT OF THE GROSS
 AREA OF THE SPACE. SPECIFY THE TOTAL SQFT OF THE SPACE
 AND THE OCCUPANT LOAD ON THE PLANS. SEE FBC TABLE
 1004.1.1
  
 6) PROVIDE SIGNED AND SEALED STRUCTURAL DETAIL DRAWINGS
 OF THE TWO NEW RECESSED CEILING AREAS SHOWING ALL
 MATERIALS AND CONNECTIONS. SEE FBC 1603 AND 1604.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]