2010-02-09 14:15:27 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| FBC-2007 EXISTING BUILDING |
| |
| 1. PLAN REVIEW FOR PRE-INSPECT INDICATES A PLUMBING |
| PERMIT IS REQUIRED. SUBMIT AN EXISTING FLOOR PLAN AND A |
| PROPOSED FLOOR PLAN TO SHOW THE EXTENT OF THE PROJECT. |
| SECTION 106.1. |
| |
| 2. IF PLUMBING PIPING IS REQUIRED, A SANITARY ISOMETRIC |
| RISER DIAGRAM AND A WATER ISOMETRIC RISER DIAGRAM WILL |
| BE REQUIRED. SECTION 106.3.5.1.3. |
| |
| 3. THE ADDRESS ON THE APPLICATION AND ON THE 17"X11" |
| DRAWING, (771 VILLAGE BLVD.) DOES NOT REFLECT THE |
| ADDRESS INDICATED IN THE CITY OF WEST PALM BEACH |
| COMMUNITY PLUS SYSTEM NOR DOES IT REFLECT THE COUNTY |
| PROPERTY APPRAISER, "PAPA" WEBSITE. PLEASE INDICATE THE |
| CORRECT ADDRESS ON ALL PLANS/APPLICATION SUBMITTED FOR |
| REVIEW. SECTION 106.1.1. |
| |
| 4. PLEASE INDICATE THE OCCUPANCY OF THE SPACE. SECTION |
| 106.3.5(2). |
| |
| 5. PER SECTION 401.4 OF THE EXISTING BUILDING CODE, A |
| DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| COMBINATION OF LEVELS OF ALEERATION PURSUANT TO |
| SECTIONS 403, 404 AND 405 OF THIS CODE. |
| |
| 6. THERE IS NOT SUFFICIENT INFORMATION TO DO A COMPLETE |
| PLAN REVIEW AT THIS TIME. MORE COMMENTS MAY BE |
| FORTHCOMING DEPENDING ON THE COMMENT RESPONSES. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |