Plan Review Notes
Plan Review Notes For Permit 10010149
Permit Number 10010149
Review Stop B
Sequence Number 2
Notes
Date Text
2010-01-28 09:57:54REVISION REQUIRED
  
 1) THE SPAN OF APPROXIMATLY 8 FEET FOR THE 3-5/8" 24
 GAGE METAL STUDS AT 16" OC FOR THE CEILING JOISTS IS
 NOT ADEQUATE. MID-SPAN BRACING OR 20 GAGE STUDS ARE
 REQUIRED. FBC R804.3.1