2010-01-19 14:49:012007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF FRAMING PLANS FOR THE PROPOSED
 NEW CEILING. SPECIFY THE MATERIALS THAT WILL BE USED,
 THE SPACING OF THE JOISTS, THE FASTENERS, THE
 ATTACHMENTS TO THE STRUCTURE, ETC. FBC 1604
  
 2) SPECIFY THE THICKNESS OF THE DRYWALL THAT WILL BE
 INSTALLED ON THE CEILING ON THE PLANS. FBC 1604
  
 NOTE: COMBUSTIBLE MATERIALS ARE NOT PERMITTED FOR ROOF
 FRAMING IN TYPE I AND II CONSTRUCTION OR IN CONCEALED
 SPACES. SEE FBC 603 AND 717.5.
  