Plan Review Notes For Permit 10010145 |
Permit Number |
10010145 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-21 14:26:40 | | | ** REDLINED PLANS FROM ORIGINAL REVIEW FROM 12/2008. | | | | WATER HEATER LOADS IS REQUIRED AT 125%. 422.13. | | WATER HEATER PROTECTION PER 422.17 | | PANEL SCHEDULE REDLINED FOR CIRCUITING PER 408.4. ALL | | CIRCUITS ARE REQUIRED TO BE SPECIFIC TO ROOMS ARE AREAS | | IN WHICH THEY FEED. FOR EXAMPLE BAY C AND B INDICATE * | | GENERAL RECEPTS* INSTEAD OF NORTH, SOUTH, WEST ETC. | | 408.4 | | | | | 2010-01-21 14:26:23 | ** RECEIVED PLANS 1/21 1PM. |
|