2010-02-03 11:20:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC1013.2, EGRESS SHALL NOT PASS THROUGH STOARAGE
 ROOMS (NEW PARTITION WALL).
  
 2. FBC1013.2, EGRESS SHALL NOT PASS THROUGH A ROOM THAN
 CAN BE LOCKED TO PREVENT ACCESS. THE DOOR AND RELATED
 HARDWARE WAS NOT INCLUDED ON THE DOOR SCHEDULE.
  
 3. SEE ISSUED PERMIT SET AND PLAN REVIEW NOTES FOR
 MASTER. THIS PERMIT WAS ISSUED WITH A PROVISO FROM THE
 PLUMBING REVIEWER, PLANS SHALL BE REVISED TO SHOW A
 FORWARD APPROACH FOR THE DRINKING FOUNTAINS. THIS
 PROVISO WAS NOT ADDRESSED, PLANS STILL SHOW A PARALLEL
 APPROACH, FBC11-4.15.5. PLEASE REVISE SHEET A2 AS
 REQUIRED.
  
 4. THIS REVISION WILL BE ISSUED WITH PROVISO -
 FBC11-4.5.2, CHANGE IN ELEVATION OF 1/2" AT EXIT DOORS
 ARE TO BE BEVELED.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  