Plan Review Notes For Permit 10010124 |
Permit Number |
10010124 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-26 11:35:04 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) THE PUMP SPECIFIED ON THE PLANS IS A HAYWARD | | SP3010EEAZ (SUPER II) AND THE PUMP CURVE SUBMITTED IS | | FOR A HAYWARD SP2710 X15 (MAX-FLO II) . PLEASE SUBMIT | | THE MANUFACTURER'S SPECIFICATIONS AND FLOW CHART FOR | | THE PUMP THAT IS SPECIFIED ON THE PLANS. | | | | 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | SYSTEM. OTHERWISE THE MAXIMUM FLOW RATE OF THE PUMP | | WILL BE USED TO DETERMINE WATER VELOCITY IN THE POOL | | PIPING. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|