2010-01-07 14:29:52RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF COMMENTS:
 A) SELECTED FLAT ROOF APPROVED SYSTEM W-26 ON SHEET 10
 OF 32 IS GOOD FOR THE DESIGN PRESSURES OF -60PSF. NEED
 TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY LIMITATION #5.6 ON SHEET 4 OF 5 TO MEET THE
 DESIGN PRESSURES AT ROOF PERIMETER AND CORNER AREAS.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 RESIDENTIAL
 CODE.
  
 2- ACCORDING TO MIAMI-DADE COUNTY WEBSITE NOA
 07-0111.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
  