Plan Review Notes For Permit 10010071 |
Permit Number |
10010071 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-07 09:31:45 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE PRODUCT APPROVAL FOR FLAT ROOF TO BE USED. | | NO INFORMATION WAS SUBMITTED. | | | | 2- CLEARLY MARK ON PRODUCT APPROVAL SPECIFIC APPROVED | | ASSEMBLY AND BASE SHEET FASTENING OPTION TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | ***NOTE 1: PROVIDE RAS 117 CALCULATIONS FOR NAIL | | ENHANCING AT PERIMETER AND CORNER AREAS IF SELECTED | | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7. (CHECK | | PRODUCT APPROVAL SUBMITTED TO SEE IF RAS 117 | | CALCULATIONS NEED TO BE SIGNED AND SEALED). IF SELECTED | | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9, THEN IT | | MAY NOT BE USED IN THIS BUILDING IF THE DESIGN | | PRESSRUES ASRE TOO LOW. | | ***NOTE 2: BUILDING IS LOCATED ON EXPOSURE "C". TAKE | | THIS INTO CONSIDERATION WHEN DOING THE RAS 117 | | CALCULATIONS. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|