Plan Review Notes For Permit 10010061 |
Permit Number |
10010061 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-12 11:02:36 | DENIED | | REFERENCE: | | FBC-2007 PLUMBING | | CODE OF ORDINANCES CITY WPB | | | | 1. PER SECTION 901.2.1 EVERY TRAP AND TRAPPED FIXTURE | | SHALL BE VENTED. THE FLOOR DRAIN SHALL BE TRAPPED. | | | | 2. PER ARTICLE III SECTION 90-125(5) STORM WATER, | | SURFACE WATER, GROUND WATER ETC. SHALL NOT DRAIN TO THE | | WASTE WATER FACILITY. | | | | 3. PER SECTION 1002.4 WHERE A TRAP SEAL IS SUBJECT TO | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | INSTALLED. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|