Plan Review Notes
Plan Review Notes For Permit 10010061
Permit Number 10010061
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-01 16:21:01** DENIED REVIEW *
  
 1) NOTE: NO DESIGN CODES ON PLANS FOR PERMIT
 APPLICATION MADE AFTER OCTOBER 1ST, 2009.
 SHOULD HAVE THE FOLLOWING AT A MINIMUM.
 2008 NFPA-70
  
 2) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS.
 FOR EXAMPLE: SHEET 8 STATES TO SEE SHEET #9 FOR
 MODIFIED ELECTRICAL POWER PANEL HOWEVER SHEET #9 HAS NO
 ELECTRICAL INFORMATION.
 PLEASE SUBMIT CIRCUITING, PANELS, LOADS, INFORMATION ON
 LIGHT POLES, BRANCH CIRCUITS, SIZES FOR CONDUCTORS,
 BREAKERS ETC.ETC.
 220,215.5.230, 225, 408.4, 310.16
  
 SECTIONS GIVEN IN GENERAL AS PLANS ARE NOT ENTIRELY
 CLEAR FOR ELECTRICAL SCOPE OF WORK.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  