 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
  
 1} INDICATE COMPLIANCE WITH THE FOLLOWING ON THE
 PLANS***13-415.AB.1.2 SPACE CONTROL. EACH SPACE
 ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT
 LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE
 GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE
 SHALL BE READILY ACCESSIBLE AND LOCATED SO THE
 OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A CONTROL
 DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY TURNS
 LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING
 A SPACE, EXCEPT SPACES WITH MULTI-SCENE CONTROL, IN THE
 FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS)
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
 B. FOR ALL OTHER SPACES, EACH CONTROL DEVICE SHALL BE
 ACTIVATED EITHER MANUALLY BY AN OCCUPANT OR
 AUTOMATICALLY BY SENSING AN OCCUPANT. EACH CONTROL
 DEVICE SHALL CONTROL A MAXIMUM OF 2,500 SQUARE FEET
 (232 M2) AREA FOR A SPACE 10,000 SQUARE FEET (929 M2)
 OR LESS AND A MAXIMUM OF 10,000 SQUARE FEET (929 M2)
 AREA FOR A SPACE GREATER THAN 10,000 SQUARE FEET (929
 M2), AND BE CAPABLE OF OVERRIDING ANY TIME-OF-DAY
 SCHEDULED SHUT-OFF CONTROL FOR NO MORE THAN FOUR HOURS
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  