Plan Review Notes For Permit 10010056 |
Permit Number |
10010056 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-05 16:53:53 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE COMPLETE PRODUCT APPROVAL FOR ROOF TILE TO | | BE INSTALLED. ONLY THE FLORIDA PRODUCT APPROVAL COVER | | PAGES WERE SUBMITTED, BUT THE REPORT THAT WAS SUBMITTED | | TO GET THE APPROVAL WAS NOT SUBMITTED. | | | | 2- SPECIFY HOW IS THE TILE GOING TO BE INSTALLED. IF | | USING NAILS OR SCREWS SPECIFY NUMBER TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. IF USING | | ADHESIVE, THEN PROVIDE THE ADHESIVE PRODUCT APPROVAL AS | | REQUIRED BY DCA RULE 9B-72. | | | | 3- FLAT ROOF PRODUCT APPROVAL SUBMITTED: CLEARLY MARK | | WHICH APPROVED ASSEMBLY IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | ***NOTE: IF SELECTED ASSEMBLY DON'T MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301, THEN SIGNED AND SEALED | | CALCULATIONS ARE REQUIRED. SEE GENERAL NOTES ON PRODUCT | | APPROVAL SUBMITTED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|