2010-01-14 15:59:14 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING | | | | 1} INDICATE DISCONNECT PER 600.6, 2008 NEC. | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | DESIGNED UNDER. 2007 FBC, 2008 NEC. SEE NOTE ON | | ENGINEERED SHEET. 106.1.3 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|