2010-01-25 13:15:45REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE STRUCTURAL DETAIL FOR ATTACHMENT OF
 CONDENSER TO SLAB FOR WIND RESISTANCE IN ACCORDANCE
 WITH FBC-M 301.12.
  
 2. PROVIDE ENERGY CODE COMPLIANCE FORM AND ATTACHED
 COOLING LOAD CALCULATIONS IN ACCORDANCE WITH FBC-B
 13-101.1.1 AND 13-407.AB.1.
  
 3. CONDENSATE SHALL DISCHARGE MIN. 12" FROM BUILDING
 STRUCTURE IN ACCORDANCE WITH FBC-B 1503.6.
  