Plan Review Notes For Permit 09120582 |
Permit Number |
09120582 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-20 15:24:03 | *****DENIED***** | | | | | | 1. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE GUARD | | SHACK'S WALLL AND CEILING IN TERMS OF CLASS A, CLASS B, | | OR CLASS C. | | | | 2. FIRE DEPARTMENT ACCESS SHALL BE PROVIDED TO THE PALM | | TRAN BUILDING THROUGH THE USE OF KNOX LOCKING GATE | | ENTRY DEVICE OR SYSTEM. CONTACT KNOX COMPANY FOR AN | | APPLICATION. | | | | 3. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN | | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 | | FEET AND 6 INCHES. | | | | 4. IF THE GUARD SHACK IS GREATER THAN 75' TRAVEL | | DISTANCE TO A PORTABLE FIRE EXTINGUISHER WITHIN THE | | PALM TRAN BUILDING, A 2A:10BC RATED FIRE EXTINGUISHER | | SHALL BE INSTALLED WITHIN OR AT THE GUARD SHACK. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|