2010-01-20 15:24:03*****DENIED*****
  
  
 1. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE GUARD
 SHACK'S WALLL AND CEILING IN TERMS OF CLASS A, CLASS B,
 OR CLASS C.
  
 2. FIRE DEPARTMENT ACCESS SHALL BE PROVIDED TO THE PALM
 TRAN BUILDING THROUGH THE USE OF KNOX LOCKING GATE
 ENTRY DEVICE OR SYSTEM. CONTACT KNOX COMPANY FOR AN
 APPLICATION.
  
 3. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET AND 6 INCHES.
  
 4. IF THE GUARD SHACK IS GREATER THAN 75' TRAVEL
 DISTANCE TO A PORTABLE FIRE EXTINGUISHER WITHIN THE
 PALM TRAN BUILDING, A 2A:10BC RATED FIRE EXTINGUISHER
 SHALL BE INSTALLED WITHIN OR AT THE GUARD SHACK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722