Date Text
2010-01-07 10:22:03 
 ** DENIED *
  
  
 1) NOTE: PLEASE BE SURE TO ADJUST CODES ON ELECTRICAL.
 SHOULD BE 2008 NEC AS OF OCTOBER 1ST, 2009.
  
 2) NOTE: PLANS ARE MISSING THE REQUIRED GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED BUILDING PER 250.32
 AND 250.50.
  
 3) NOTE: PLEASE SEE 2008 NEC 406.8 A AND B FOR WEATHER
 RESISTANT RECEPTACLES NOW REQUIRED.
  
 4) NOTE: PLEASE SEE 2008 NEC 250.94 FOR REQUIRED
 INTER-SYSTEM BONDING.
  
 5) NOTE: PLEASE SHOW TOTAL LOAD ON THE 125MCB PANEL
 WHICH FEEDS NEW SUB PANEL.
 220
  
 6) NOTE: EXTERIOR LIGHTING CONTROL(S) REQUIRED TO MEET
 FBC 13-415.AB.1.4
  
 7) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS/ FLA COM
 ENERGY CALCULATIONS SUBMITTED. PLEASE SEE 13-415.AB.5
 FOR INTERIOR LIGHTING. PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR BUILDING AND MECHANICAL SYSTEMS TO BE SHOWN
 IN FLA COM REPORT.
 13-400, 13-101,13-103 ETC
  
  
  
  
 PLEASE CALL TO GO OVER FOR ANY QUESTIONS. THE
 ALLOWANCES UNDER THE 2007 FBC W/ 2009 SUPPLEMENTS HAVE
 COMPLETELY CHANGED FROM PREVIOUS CODES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  