Plan Review Notes For Permit 09120582 |
Permit Number |
09120582 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-07 10:22:03 | | | ** DENIED * | | | | | | 1) NOTE: PLEASE BE SURE TO ADJUST CODES ON ELECTRICAL. | | SHOULD BE 2008 NEC AS OF OCTOBER 1ST, 2009. | | | | 2) NOTE: PLANS ARE MISSING THE REQUIRED GROUNDING | | ELECTRODE SYSTEM AT THE DETACHED BUILDING PER 250.32 | | AND 250.50. | | | | 3) NOTE: PLEASE SEE 2008 NEC 406.8 A AND B FOR WEATHER | | RESISTANT RECEPTACLES NOW REQUIRED. | | | | 4) NOTE: PLEASE SEE 2008 NEC 250.94 FOR REQUIRED | | INTER-SYSTEM BONDING. | | | | 5) NOTE: PLEASE SHOW TOTAL LOAD ON THE 125MCB PANEL | | WHICH FEEDS NEW SUB PANEL. | | 220 | | | | 6) NOTE: EXTERIOR LIGHTING CONTROL(S) REQUIRED TO MEET | | FBC 13-415.AB.1.4 | | | | 7) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS/ FLA COM | | ENERGY CALCULATIONS SUBMITTED. PLEASE SEE 13-415.AB.5 | | FOR INTERIOR LIGHTING. PLEASE SEE COMMENTS FROM OTHER | | TRADES FOR BUILDING AND MECHANICAL SYSTEMS TO BE SHOWN | | IN FLA COM REPORT. | | 13-400, 13-101,13-103 ETC | | | | | | | | | | PLEASE CALL TO GO OVER FOR ANY QUESTIONS. THE | | ALLOWANCES UNDER THE 2007 FBC W/ 2009 SUPPLEMENTS HAVE | | COMPLETELY CHANGED FROM PREVIOUS CODES. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | |
|