2010-01-06 15:30:592007 FBC W/2007 REVISIONS
 INSTALL NEW HVAC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF MANUAL J OR OTHER APPROVED
 HEATING AND COOLING EQUIPMENT SIZING METHODOLOGIES AS
 REQUIRED BY FBC R M1401.3.
  
 2) SUBMIT CLEAR AND LEGIBLE PLANS WHICH SPECIFY THE
 DUCT SIZES, THE GRILL SIZES AND LOCATIONS, THE CFMS AT
 SUPPLY GRILL, ETC. THE PLANS THAT WERE SUBMITTED HAVE
 TOO MUCH OTHER INFORMATION ON THEM WHICH OBSCURES THE
 MECHANICAL INFORMATION. DON'T SHOW THE DUCT INFORMATION
 FOR THE FIRST FLOOR ON THE SECOND FLOOR PLAN. IF THE
 GRILLS ARE LOCATED IN THE SIDEWALL DON'T SHOW THEM IN
 THE MIDDLE OF THE ROOM. FBC R M1601.1
  
 3) THE 10 X 6 THROUGH WALL TRANSFER GRILLS SHOWN ON
 PLANS AT BEDROOMS WITH 250 CFM SUPPLY AIR, DOES NOT
 COMPLY WITH FBC R M1602.4. TRANSFER GRILLES SHALL USE
 50 SQUARE INCHES OF GRILL AREA TO 100 CFM OF SUPPLY
 AIR.
  