Plan Review Notes
Plan Review Notes For Permit 09120528
Permit Number 09120528
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-30 11:47:482007 FBC W/2009 REVISIONS
 PLUMBING REVISIONS
  
 DENIED
  
 1) TWO SETS OF REVISED PLANS ARE REQUIRED. FBC 106.1
 CITY AMENDMENTS
  
 2) PLEASE INDICATE CHANGES FROM THE APPROVED PLANS WITH
 CLOUDS OR OTHER ACCEPTABLE METHODS.
  
 3) THE PLUMBING RISER DIAGRAM DOES NOT MATCH THE
 ARCHITECTURAL PLANS.
  
 4) SPECIFY ALL DWV PIPE SIZES ON THE PLANS. FBCR
 P3005.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]