Plan Review Notes For Permit 09120528 |
Permit Number |
09120528 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-30 12:21:03 | 2007 FBC W/2009 REVISIONS | | MECHANICAL REVISIONS | | | | DENIED | | | | 1) TWO SETS OF OF REVISED PLANS ARE REQUIRED. | | | | 2) MECHANICAL VENTILATION DISCHARGED TO THE EXTERIOR IS | | REQUIRED IN THE BATHROOMS PER FBCR M 1507.2. THE | | EXHAUST CAPACITY OF 50 CFM INTERMITTENT IS REQUIRED PER | | M 1507.3. | | | | 3) TRANSFER DUCTS ARE REQUIRED TO BE TO BE 1.5 TIMES | | THE CROSS SECTIONAL AREA OF THE SUPPLY DUCT ENTERING | | THE ROOM. PLEASE REVISE. SEE FBCR M 1602.4. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|