2010-01-14 10:37:23REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CONDENSING UNITS ORIGINALLY SHOWN AS GROUND-MOUNTED,
 NOW SHOWN AS MOVED TO THE ROOF. THESE UNITS ARE WITHIN
 10 FEET OF THE ROOF EDGE AND GUARDS ARE REQUIRED IN
 ACCORDANCE WITH FBC-M 304.10.
  
 2. ROOF STAND FOR CONDENSERS IS NOW SHOWN ON PLANS.
 PROVIDE COMPLETE ENGINEERING DETAIL FOR CONSTRUCTION OF
 THE STAND AND ATTACHMENT OF THE CONDENSERS TO THE STAND
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.13.
 ALTERNATIVELY, IF A PRE-ENGINEERED A/C STAND IS USED,
 PROVIDE PRODUCT APPROVAL DOCUMENTATION IN ACCORDANCE
 WITH FBC-B 106.3.3 AND FAC RULE 9B-72.
  
 3. EXHAUST FANS FOR THE TOILET ROOMS HAVE BEEN
 ELIMINATED FROM THE PLANS. SHOW HOW THE REQUIRED
 EXHAUST IS TO BE PROVIDED IN THESE SPACES PER FBC-M
 TABLE 403.3.
  
 4. THE SIZE, AND LOCATION OF OUTSIDE AIR DUCTS ARE NOT
 SHOWN ON THE PLANS. ALSO, THE LOCATION OF OUTSIDE AIR
 INTAKES IS NOT SHOWN ON THE PLANS. SHOW MISSING
 INFORMATION TO DEMONSTRATE COMPLIANCE WITH FBC-M 603.1
 AND FBC-M 401.5.
  
 5. RETURN AIR FLEX DUCT SIZES ARE NOT SHOWN ON PLANS.
 PROVIDE MISSING INFORMATION TO DEMONSTRATE COMPLIANCE
 WITH FBC-M 601.4 AND 603.1.
  
 6. DUE TO THE RELOCATION OF THE CONDENSERS TO THE ROOF,
 A ZONING REVIEW IS REQUIRED.
  