2010-01-12 14:24:38 | ****PROVISO**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. THE PAVILLIONS ARE TO BE LOCATED ON AN ACCESSIBLE |
| ROUTE, FBC11-4.1.2(2). (NO RESPONSE OR ACTION REQUIRED) |
| |
| 2. FBC1802.2, PROVIDE TWO ORIGINAL SOILS REPORTS. |
| (PROVIDE AT INSPECTION) |
| |
| 3. FAC9B72, PROVIDE PRODUCT APPROVAL FOR THE ROOF. WIND |
| DESIGN CRITERIA (COMPONENTS & CLADDING PRESSURES) |
| REQUIRED FOR THE ROOF, FBC1603.1.4. SEE ALSO ITEM 4. |
| PRIOR TO SUBMITTAL, THE PRODUCT APPROVALS SHOULD BE |
| REVIEWED BY DESIGNER OF RECORD. ALSO, PRIOR TO |
| SUBMITTAL, DESIGNER OF RECORD IS TO CONFIRM WITH THE |
| METAL ROOF MANUFACTURER THAT THE PRODUCT IS SUITABLE |
| FOR THIS PROJECT (COASTAL/CORROSIVE) OR LETTER FROM DOR |
| OR OWNER STATING THAT THIS ISSUE HAS BEEN INVESTIGATED. |
| (PRIOR TO FINAL INSPECTION) |
| |
| 4. PAGE LD2 HAS A NOTE WHICH STATES "REFER TO ANCHOR |
| AND FOOTING DOWLOAD SHEETS FOR GENERAL INFORMATION . . |
| . " (ETC.). THESE SHEETS WERE NOT SUBMITTED. NO |
| STRUCTURAL INFORMATION REGARDING THE PROPOSED SHELTER |
| OR FOOTING WAS SUBMITTED. DETAILS ON LD1 ARE FOR THE |
| 10X10 TENNIS SHELTER (NOT THE 20X20 PICNIC SHELTERS). A |
| REVISION IS REQUIRED PRIOR TO FINAL INSPECTION - |
| MINIMUM DESIGN CRITERIA IS 140MPH EXPOSURE C. (PRIOR TO |
| FINAL INSPECTION) |
| |
| |