Plan Review Notes For Permit 09120493 |
Permit Number |
09120493 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-29 08:48:16 | REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- ACCORDING TO THE DBPR WEBSITE THE LICENSE IS | | CURRENTLY SUSPENDED. CONTRACTOR NEEDS TO UPDATE | | INFORMATION WITH THE DBPR PRIOR TO OBTAINING A PERMIT. | | | | 2- ACCORDING TO THE MIAMI-DADE NOA 07-1203.01 SUBMITTED | | WAS SUPERSEDED. GO TO THE MIAMI-DADE WEBSITE AND | | PROVIDE CURRENT NOA. | | | | 3- MODIFIED BITUMEN ROOF SYSTEM PROVIDED: | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 OF | | 2007 FBC. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. 1609 OF 2007 FBC. | | | | 4- PROVIDE SKETCH SHOWING LOCATION OF AREA TO RECEIVE | | THE FLAT ROOF AS REQUIRED BY SEC. 106.1.1 CITY | | AMENDMENTS TO FBC. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|