Plan Review Notes For Permit 09120486 |
Permit Number |
09120486 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-28 09:55:28 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- A) MODIFIED BITUMEN ASSEMBLY SELECTED ON SHEET 30 OF | | 34 OF NOA 05-0830.10 CAN NOT BE USED IN THIS BUILDING | | BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES REQUIRED | | BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. APPROVED | | ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION #9 | | CAN'T BE ENHANCED TO INCREASE THE DESIGN PRESSURES. SEE | | GENERAL LIMITATION #9 ON LAST PAGE OF NOA SUBMITTED. | | | | B) ONLY APPROVED ASSEMBLIES THAT ARE LIMITED BY GENERAL | | LIMITATION #7 ARE ALLOWED TO DO NAIL ENHANCING. SEE | | GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | SELECT ANOTHER APPROVED ASSEMBLY AND PROVIDE THE RAS | | 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND | | CORNER AREAS. | | | | 2- FLORIDA PRODUCT APPROVAL FL10674 SUBMITTED IS | | PENDING FBC APPROVAL. PROVIDE CURRENT COPY WITH | | APPROVED STATUS. GO THE WWW.FLORIDABUILDING.ORG WEBSITE | | TO DOWNLOAD CURRENT PRODUCT APPROVAL. | | | | 3- PROPERTY IS LOCATED ON THE HISTORIC DISTRICT. | | PLEASE, OBTAIN HISTORICAL APPROVAL STAMP PRIOR TO | | SUBMITTAL TO THIS OFFICE. | | | | 4- THIS PERMIT IS NOT ONLY TO ROOF NEW ADDITION , BUT | | TO REROOF EXISTING HOUSE. OWES $307.43 FOR THE REROOF | | PERMIT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 | | | | |
|