Plan Review Notes
Plan Review Notes For Permit 09120475
Permit Number 09120475
Review Stop M
Sequence Number 2
Notes
Date Text
2010-03-04 09:56:04**PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR CONDENSING UNIT AND
 ROOF CAP SHOWING THESE TO BE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 2. PAGE M-2 AHU INSTALLATION DETAIL STILL CALLS FOR
 CONDENSATE TO DISCHARGIN INTO HUB DRAIN. CONDENSATE
 SHALL NOT DISCHARGE INTO SANITARY SEWER SYSTEM PER
 FBC-M 307.2.1 AND CITY ORDINANCE.
  