Date |
Text |
2010-02-11 16:26:03 | *DENIED ** |
| |
| 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR DEVICE |
| LOCATIONS FOR HORNS, STROBES, HORN/STROBES ETC. |
| LOCATIONS SHOWN ON PLANS DO NOT MEET MINIMUM FOR ADA. |
| ALL LOCATIONS WHICH ARE ACCESSIBLE SHALL HAVE COVERAGE. |
| DEVICE HEIGHTS, ALONG WITH PULL STATION HEIGHTS ARE |
| ALSO REQUIRED. |
| |
| 2) NOTE: PLEASE COORDINATE PANELS. RISER INDICATES |
| 200AMP MLO, HOWEVER PANELS ARE SHOWN AS 225AMP. |
| 215.5. |
| ** THIS WOULD HAVE BEEN REDLINE DIF ONLY COMMENT. |
| |
| 3) NOTE: LIGHTING CONTROLS STILL REQUIRED TO MEET FBC |
| 13-415.AB.1.1,.1.2 AND .1.3. |
| PLEASE SEE .1.3, THE ADDITIONAL CONTROLS FOR LIGHTING |
| SUCH AS FIXTURE B. THE ROCKER SWITCH ON FIXTURE B IS |
| NOT ACCEPTABLE TO MEET MINIMUM CODE. |
| |
| 4) NOTE: THE FIXTURE LEGEND INDICATES A NEW FIXTURE *C* |
| HOWEVER COULD NOT LOCATE THIS ON PLANS. |
| 13-415.AB.5. CAN NOT CONFIRM ATTACHED METHOD B AS |
| COMPLIANT AT THIS TIME. |
| |
| 5) NOTE: THE PREVIOUS NOTES MENTIONED THAT ROOM NOW |
| LABELED AS STORAGE DID NOT MEET NEC 645 OR NFPA-75 FOR |
| DEFINITIONS AS AN IT ROOM. HOWEVER THIS ROOM COULD BE |
| LABELED AS TELEPHONE ROOM, TELCOM ROOM, COMPUTER ROOM |
| ETC. PLANS NOW LABEL THIS AS A *STORAGE ROOM*. IS THIS |
| TRUE WITH ALL OF THE ELECTRICAL AND OVER CURRENT |
| PROTECTION SHOWN ON PLANS? PLEASE SEE 240.24 FOR |
| LOCATION OF OVER CURRENT PROTECTION DEVICES NOT |
| PERMITTED IN STORAGE ROOM |
| PLEASE CALL TO GO OVER. |
| |
| |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |