2010-02-11 16:26:03*DENIED **
  
 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR DEVICE
 LOCATIONS FOR HORNS, STROBES, HORN/STROBES ETC.
 LOCATIONS SHOWN ON PLANS DO NOT MEET MINIMUM FOR ADA.
 ALL LOCATIONS WHICH ARE ACCESSIBLE SHALL HAVE COVERAGE.
 DEVICE HEIGHTS, ALONG WITH PULL STATION HEIGHTS ARE
 ALSO REQUIRED.
  
 2) NOTE: PLEASE COORDINATE PANELS. RISER INDICATES
 200AMP MLO, HOWEVER PANELS ARE SHOWN AS 225AMP.
 215.5.
 ** THIS WOULD HAVE BEEN REDLINE DIF ONLY COMMENT.
  
 3) NOTE: LIGHTING CONTROLS STILL REQUIRED TO MEET FBC
 13-415.AB.1.1,.1.2 AND .1.3.
 PLEASE SEE .1.3, THE ADDITIONAL CONTROLS FOR LIGHTING
 SUCH AS FIXTURE B. THE ROCKER SWITCH ON FIXTURE B IS
 NOT ACCEPTABLE TO MEET MINIMUM CODE.
  
 4) NOTE: THE FIXTURE LEGEND INDICATES A NEW FIXTURE *C*
 HOWEVER COULD NOT LOCATE THIS ON PLANS.
 13-415.AB.5. CAN NOT CONFIRM ATTACHED METHOD B AS
 COMPLIANT AT THIS TIME.
  
 5) NOTE: THE PREVIOUS NOTES MENTIONED THAT ROOM NOW
 LABELED AS STORAGE DID NOT MEET NEC 645 OR NFPA-75 FOR
 DEFINITIONS AS AN IT ROOM. HOWEVER THIS ROOM COULD BE
 LABELED AS TELEPHONE ROOM, TELCOM ROOM, COMPUTER ROOM
 ETC. PLANS NOW LABEL THIS AS A *STORAGE ROOM*. IS THIS
 TRUE WITH ALL OF THE ELECTRICAL AND OVER CURRENT
 PROTECTION SHOWN ON PLANS? PLEASE SEE 240.24 FOR
 LOCATION OF OVER CURRENT PROTECTION DEVICES NOT
 PERMITTED IN STORAGE ROOM
 PLEASE CALL TO GO OVER.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  