Plan Review Notes
Plan Review Notes For Permit 09120475
Permit Number 09120475
Review Stop P
Sequence Number 1
Notes
Date Text
2010-01-07 14:30:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1 ADMIN.
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE OF ORDINANCES
  
 1. ALL ARCHITECTURAL SHEETS, SHEET M 1 & ALL ELECTRICAL
 SHEETS. PER FAC 61G1-16.004(2)(6) THE FIRM LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), AND PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. FS 481.2055.
  
 2. SHEETS M 2, P 1 & P 2 A TITLE BLOCK MUST APPEAR ON
 ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND
 SPECIFICATION IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TLEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 THE ABOVE SHEETS HAVE NO TITLE BLOCK AS REQUIRED. FS
 481.2055.
  
 3. SHT P 1 SHOWS CONDENSATE FROM HVAC-1 DRAINING TO
 MS-1. THIS IS NOT APPROVED PER CITY CODE ARTICLE III
 SECTION 90-124. THE CONDENSATE SHALL DRAIN FROM THE
 BUILDING SEPARATELY AND TERMINATE IN A DRYWELL, A STORM
 DRAIN, (RELIEF VENT REQUIRED AS CONDENSATE EXITS THE
 BUILDING), OR TO A PLANTED AREA.
  
 4. SHTS P 1 & P 2 THE VENT FOR THE MOP SINK. PER
 SECTION 905.4 EVER DRY VENT SHALL RISE VERTICALLY TO A
 MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE PLANS
 SHOW THE VENT RUNNING HORIZONTALLY UNDER THE SLAB.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM AS REQUIRED
 IN SECTION 106.3.5.1.3. SHOW ALL PIPE SIZE, VALVES AND,
 (WHERE REQUIRED BY SECTION 604.9) WATER HAMMER
 ARRESTORS). WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved