Date |
Text |
2010-01-07 14:30:28 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 ADMIN. |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| CITY WPB CODE OF ORDINANCES |
| |
| 1. ALL ARCHITECTURAL SHEETS, SHEET M 1 & ALL ELECTRICAL |
| SHEETS. PER FAC 61G1-16.004(2)(6) THE FIRM LICENSE |
| NUMBER, (CERTIFICATE OF AUTHORIZATION), AND PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| THE TITLE BLOCK OF EACH SHEET. FS 481.2055. |
| |
| 2. SHEETS M 2, P 1 & P 2 A TITLE BLOCK MUST APPEAR ON |
| ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND |
| SPECIFICATION IDENTIFICATION SHEETS. THE TITLE BLOCK |
| MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TLEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| THE ABOVE SHEETS HAVE NO TITLE BLOCK AS REQUIRED. FS |
| 481.2055. |
| |
| 3. SHT P 1 SHOWS CONDENSATE FROM HVAC-1 DRAINING TO |
| MS-1. THIS IS NOT APPROVED PER CITY CODE ARTICLE III |
| SECTION 90-124. THE CONDENSATE SHALL DRAIN FROM THE |
| BUILDING SEPARATELY AND TERMINATE IN A DRYWELL, A STORM |
| DRAIN, (RELIEF VENT REQUIRED AS CONDENSATE EXITS THE |
| BUILDING), OR TO A PLANTED AREA. |
| |
| 4. SHTS P 1 & P 2 THE VENT FOR THE MOP SINK. PER |
| SECTION 905.4 EVER DRY VENT SHALL RISE VERTICALLY TO A |
| MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE |
| HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE PLANS |
| SHOW THE VENT RUNNING HORIZONTALLY UNDER THE SLAB. |
| |
| 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM AS REQUIRED |
| IN SECTION 106.3.5.1.3. SHOW ALL PIPE SIZE, VALVES AND, |
| (WHERE REQUIRED BY SECTION 604.9) WATER HAMMER |
| ARRESTORS). WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE |
| CEILING. PDI-WH 201. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |