2010-01-19 16:36:30REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 AND "MECHANIACL CODE NOTES" #5 CALLS FOR
 DUCT SMOKE DETECTORS TO BE INSTALLED ON THE RETURN
 DUCT. SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY
 AIR SYSTEM IN ACCORDANCE WITH FBC-M 606.2.1.
  
 2. PAGE M1 SHOWS EXHAUST DUCTS LOCATED IN THE RETURN
 AIR PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE WITH
 FBC-M 601.5.
  
 3. PAGE M1 SHOWS EF-3 TO NEW CURB AND ROOF CAP. ROOF
 CURB AND CAP SHALL BE DESIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 STRUCTURAL INSTALLATION DETAIL FOR THE NEW ROOF CURB
 AND MANUFACTURER'S DATA WITH INSTALLATION INSTRUCTIONS
 SHOWING WIND RESISTANCE CAPABILITIES OF THE PROPOSED
 ROOF CAP.
  
 4. HVAC-1 CONDENSING UNIT IS PROPOSED FOR ROOF
 INSTALLATION. PROVIDE STRUCTURAL INSTALLATION DETAIL
 FOR WIND RESISTANT INSTALLATION OF CONDENSER IN
 ACCORDANCE WITH FBC-M 301.12. ALSO PROVIDE
 MANUFACTURER'S DATA SHOWING THE CONDENSER IS DESIGNED
 FOR WIND RESISTANCE. IF A PRE-ENGINEERED ROOF STAND IS
 USED, PROVIDE PRODUCT APPROVAL IN ACCORDANCE WITH FBC-B
 106.3.3 AND FAC RULE 9B-72.
  
 5. NEW CONDENSING UNIT ON THE ROOF SHALL COMPLY WITH
 THE REQUIREMENTS FOR GUARDS IF WITHIN 10 FEET OF THE
 ROOF EDGE IN ACCORDANCE WITH FBC-M 304.10. PERMANENT
 MEANS OF ACCESS MAY ALSO BE REQUIRED IN ACCORDANCE WITH
 FBC-M 306.5. PROVIDE ROOF PLAN SHOWING PROPOSED
 INSTALLATION LOCATION OF CONDENSING UNIT.
  
 6. PAGE M2 NOTE CALLS FOR HVAC-1 CONDENSATE TO
 DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE.
 CONDENSATE SHALL BE DISCHARGED IN AN APPROVED LOCATION
 IN ACCORDANCE WITH FBC-M 307.2.1.
  
 7. PLANS SHOW EXHAUST DUCTS WITHIN THE RETURN AIR
 PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH A PLENUM IN ACCORDANCE WITH
 FBC-M 601.5.
  
 8. PLANS SHALL BE PROPERLY SIGNED AND SEALED WITH
 ORIGINAL SIGNATURE IN ACCORDANCE WITH FS 481. FULL
 TITLE BLOCK INFORMATION AND CERTIFICATE OF
 AUTHORIZATION NUMBER ARE ALSO REQUIRED.
  