Plan Review Notes
Plan Review Notes For Permit 09120475
Permit Number 09120475
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-01-20 13:34:48*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2007 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM
 FIRE CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE,
 2006 EDITION SHALL BE REFERENCED.
  
 3. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIAL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4. ON THE FLOOR PLAN AND/OR EQUIPMENT PLAN, SHOW THE
 LOCATION OF THE PORTABLE FIRE EXTINGUISHER(S) WHICH
 SATISFY THE 75' TRAVEL DISTANCE.
  
 5. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 6. THE 2002 OF NFPA 72 - NATIONAL FIRE ALARM CODE -
 SHALL BE REFERENCED.
  
 7. CORRELATE SYMBOLS FOR FIRE ALARM HORN STROBES ON
 SHEET E-1 WITH THE ELECTRICAL SYMBOLS SHOWN ON THE E-4
 SHEET.
  
 8. PLEASE EXPLAIN WHY NO VISUAL STROBES ARE SHOWN IN
 THE TOILETS/BATHROOMS/RESTROOMS (SHEET E-1) .
  
 9. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 CODE COMPLIANCE. THESE DEVICES MAY BE SHOWN ON THE
 REFLECTED CEILING PLAN SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED ON THE
 THE APPROPIATE PLAN SHEET.
  
  