2010-01-20 13:34:48 | *****DENIED***** |
| |
| |
| 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| EDITION. |
| |
| 2. EFFECTIVE 12/31/2008, THE 2007 EDITION OF THE |
| FLORIDA FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM |
| FIRE CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, |
| 2006 EDITION SHALL BE REFERENCED. |
| |
| 3. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIAL IN |
| TERMS OF CLASS A, CLASS B, OR CLASS C. |
| |
| 4. ON THE FLOOR PLAN AND/OR EQUIPMENT PLAN, SHOW THE |
| LOCATION OF THE PORTABLE FIRE EXTINGUISHER(S) WHICH |
| SATISFY THE 75' TRAVEL DISTANCE. |
| |
| 5. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL |
| INITIATE A GENERAL FIRE ALARM. |
| |
| 6. THE 2002 OF NFPA 72 - NATIONAL FIRE ALARM CODE - |
| SHALL BE REFERENCED. |
| |
| 7. CORRELATE SYMBOLS FOR FIRE ALARM HORN STROBES ON |
| SHEET E-1 WITH THE ELECTRICAL SYMBOLS SHOWN ON THE E-4 |
| SHEET. |
| |
| 8. PLEASE EXPLAIN WHY NO VISUAL STROBES ARE SHOWN IN |
| THE TOILETS/BATHROOMS/RESTROOMS (SHEET E-1) . |
| |
| 9. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR |
| CODE COMPLIANCE. THESE DEVICES MAY BE SHOWN ON THE |
| REFLECTED CEILING PLAN SHEET. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED ON THE |
| THE APPROPIATE PLAN SHEET. |
| |
| |