Plan Review Notes
Plan Review Notes For Permit 09120475
Permit Number 09120475
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-30 16:21:50 
 ** DENIED *
  
  
  
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION WITHOUT
 A LICENSED CONTRACTOR UNDER *TBD* (TO BE DETERMINED).
 EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT REVIEW
 WILL STILL REMAIN IN FAILED STATUS UNTIL LICENSED
 CONTRACTOR HAS APPLIED.
  
 2) NOTE: BOTH SETS OF PLANS SUBMITTED DO NOT CONTAIN AN
 ORIGINAL SIGNATURE BY THE LICENSED DESIGN PROFESSIONAL.
 THE USE OF A *RUBBER-STAMP* IS NOT PERMITTED.
 FS 481.221
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE
 REVIEW.
  
 3) NOTE: THE SUBMITTED FLA COM METHOD B CALCULATIONS
 ALSO CONTAIN A RUBBER STAMP FOR THE ARCHITECT OF
 RECORD. THESE ARE ALSO NOT SEALED WITH THE RAISED SEAL
 AS REQUIRED.
 FS 481.221, FAC 61G1-16.002. FBC 13-103.1
  
 4) NOTE: THE ARCHITECTURAL FIRM LISTED ON THE TITLE
 BLOCKS ARE REQUIRED TO DISPLAY THE FIRM LICENSED NUMBER
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 WHICH REQUIRES THE INFORMATION TO BE LOCATED ON TITLE
 BLOCKS. PLEASE SEE FLORIDA STATUTES 481.219 WHICH
 REQUIRES THE FIRM TO HAVE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEW.
  
 5) NOTE: PLEASE SEE SHEET T1. THE PLANS CONTAINS
 RELEVANT CODES FOR ELECTRICAL AS THE 2008 AND 2005
 NFPA-70.
 PLEASE KNOW THAT ON OCTOBER 1ST, 2009 THE SECOND SET OF
 2009 SUPPLEMENTS TO THE FLORIDA BUILDING CODE WAS
 ADOPTED. THIS INCLUDES THE ADOPTION OF THE 2008
 NFPA-70.
 ** PLEASE ADJUST CODES ON PLANS.
 OTHER RELEVANT CODES ON PLANS SHALL BE LISTED AS
 FOLLOWS.
  
 2006 NFPA-101 ( LIFE SAFETY CODE)
 2002 NFPA-72 ( NATIONAL FIRE ALARM CODE)
 2007 FLORIDA FIRE PREVENTION CODE.
  
 ADOPTED BY FBC AND FAC 69A-60.004, 69A-03.012
  
 6) NOTE: ROOM 008 IS LABELED AS AN IT ROOM ON PLANS.
 PLEASE SEE NFPA-75 2003 EDITION AND 2008 NFPA-70 FOR
 DEFINITIONS OF AN *IT ROOM*. PLEASE SEE NEC 645.4
 (1-5). THE NEC SPECIFICALLY IN 645 ALLOWS LESS
 STRINGENT WIRING METHODS THAN REQUIRED IN CHAPTERS 1-4
 OF THE NEC. HOWEVER IN ORDER TO CONSIDERED AN IT ROOM
 BY DEFINITION, ALL CONSTRUCTION MUST MEET NFPA-75 AND
 ALL ITEMS LISTED IN 645.4(1-5) MUST BE MET. BASED ON
 THE PLANS SUBMITTED THIS LOCATION DOES NOT MEET THE
 MINIMUM REQUIREMENTS TO BE CONSIDERED AN IT ROOM.
  
 ** IF THIS IS NOT GOING TO BE AN IT ROOM BY DEFINITION,
 PLEASE ADJUST ROOM DESIGNATION AND PLEASE PLACE NOTE ON
 ELECTRICAL PLANS WHICH STATES: *NO WIRING METHODS PER
 NEC 645 PERMITTED*, OR WORDS TO THAT AFFECT.
 PLEASE CALL TO GO OVER ANY QUESTIONS.
  
 7) NOTE: PLEASE INDICATE ALL CIRCUITS ON PLANS AND
 COORDINATE WITH PANEL SCHEDULES. BRANCH CIRCUIT LOADS,
 WIRING ETC CAN NOT BE FULLY VERIFIED AT THIS TIME.
 E 1.1 INDICATES THIS AS A CABLING PLAN. THERE IS NO
 POWER PLAN AND POWER FOR RECEPTACLES IS ALL SHOWN ON
 E1.1. PLEASE COMPLETE.
 NEC 240.4, 310.16, 408.4, 210.19, 210.20, 210.21 ETC
 PLEASE BE SURE TO SEE THE FOLLOWING FROM NEC 408.4
 WHICH DOES NOT PERMIT THE GENERAL DESCRIPTION AS
 *RECEPTACLES* OR *LIGHTS*. ALL AREAS ARE REQUIRED TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH EACH BREAKER
 FEEDS. EXAMPLE: LF-7, OFFICE 004 RECEPTACLES. THESE MAY
 BE ALPHA OR NUMERIC DESIGNATIONS.
 ** TEXT FROM CODE COMMENTARY IN THE NEC*
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE 210.8B1-5 WHICH REQUIRES GFI
 RECEPTACLES OR GFI PROTECTION. RECEPTACLES IN LOCATIONS
 SUCH AS KITCHEN BREAK AREAS, BATHROOMS AND ALL
 RECEPTACLES WITHIN 6FT OF OTHER SINKS ARE ALL REQUIRED.
  
 9) NOTE: PLANS CONTAIN NOTES FOR FIRE ALARM HOWEVER
 NONE SHOWN ON PLANS. EVEN THOUGH FIRE ALARM PERMITS ARE
 SEPARATE ALONG WITH SEPARATE SHOP DRAWINGS, THE BASE
 PLANS ARE ALL REQUIRED TO SHOW MINIMUM REQUIRED FOR
 DESIGN INTENT. FS 633
 PLEASE SHOW ALL LOCATIONS, HEIGHTS AND MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3.
  
 10) NOTE: PLEASE INCLUDE NOTES FOR WIRING PER NEC 517,
 PART II. PER THE SCOPE OF WORK AND OCCUPANCY WIRING
 SHALL CONTAIN REDUNDANT GROUNDING PER 517.13.
  
 11) NOTE: RISER INDICATES TWO METERS AND TENANT
 DISCONNECTS FOR ONE TENANT SPACE. NOTES ON PLANS STATE
 THESE AS * SERVICES* HOWEVER PER NEC 100 THESE ARE NOT
 SERVICES. PLEASE VERIFY WITH FIRE MARSHAL THAT MORE
 THAN ONE DISCONNECTING MEANS WILL BE PERMITTED FOR ONE
 TENANT SPACE.
  
 12) NOTE: THE AIR CONDITIONING EQUIPMENT IS SHOWN ON
 M-SHEETS HOWEVER NOT ON ELECTRICAL SHEETS. IN FACT
 THERE ARE MORE BREAKERS FOR A/C EQUIPMENT IN PANEL HC
 THAN SHOWN ON RISER.
 IT IS UNCLEAR WHERE THE OTHER BRANCH CIRCUITS LISTED ON
 PANEL HC IS?
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  