Date |
Text |
2009-12-30 16:21:50 | |
| ** DENIED * |
| |
| |
| |
| |
| |
| 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION WITHOUT |
| A LICENSED CONTRACTOR UNDER *TBD* (TO BE DETERMINED). |
| EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT REVIEW |
| WILL STILL REMAIN IN FAILED STATUS UNTIL LICENSED |
| CONTRACTOR HAS APPLIED. |
| |
| 2) NOTE: BOTH SETS OF PLANS SUBMITTED DO NOT CONTAIN AN |
| ORIGINAL SIGNATURE BY THE LICENSED DESIGN PROFESSIONAL. |
| THE USE OF A *RUBBER-STAMP* IS NOT PERMITTED. |
| FS 481.221 |
| ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE |
| REVIEW. |
| |
| 3) NOTE: THE SUBMITTED FLA COM METHOD B CALCULATIONS |
| ALSO CONTAIN A RUBBER STAMP FOR THE ARCHITECT OF |
| RECORD. THESE ARE ALSO NOT SEALED WITH THE RAISED SEAL |
| AS REQUIRED. |
| FS 481.221, FAC 61G1-16.002. FBC 13-103.1 |
| |
| 4) NOTE: THE ARCHITECTURAL FIRM LISTED ON THE TITLE |
| BLOCKS ARE REQUIRED TO DISPLAY THE FIRM LICENSED NUMBER |
| ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| WHICH REQUIRES THE INFORMATION TO BE LOCATED ON TITLE |
| BLOCKS. PLEASE SEE FLORIDA STATUTES 481.219 WHICH |
| REQUIRES THE FIRM TO HAVE THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| ANY OTHER TRADE REVIEW. |
| |
| 5) NOTE: PLEASE SEE SHEET T1. THE PLANS CONTAINS |
| RELEVANT CODES FOR ELECTRICAL AS THE 2008 AND 2005 |
| NFPA-70. |
| PLEASE KNOW THAT ON OCTOBER 1ST, 2009 THE SECOND SET OF |
| 2009 SUPPLEMENTS TO THE FLORIDA BUILDING CODE WAS |
| ADOPTED. THIS INCLUDES THE ADOPTION OF THE 2008 |
| NFPA-70. |
| ** PLEASE ADJUST CODES ON PLANS. |
| OTHER RELEVANT CODES ON PLANS SHALL BE LISTED AS |
| FOLLOWS. |
| |
| 2006 NFPA-101 ( LIFE SAFETY CODE) |
| 2002 NFPA-72 ( NATIONAL FIRE ALARM CODE) |
| 2007 FLORIDA FIRE PREVENTION CODE. |
| |
| ADOPTED BY FBC AND FAC 69A-60.004, 69A-03.012 |
| |
| 6) NOTE: ROOM 008 IS LABELED AS AN IT ROOM ON PLANS. |
| PLEASE SEE NFPA-75 2003 EDITION AND 2008 NFPA-70 FOR |
| DEFINITIONS OF AN *IT ROOM*. PLEASE SEE NEC 645.4 |
| (1-5). THE NEC SPECIFICALLY IN 645 ALLOWS LESS |
| STRINGENT WIRING METHODS THAN REQUIRED IN CHAPTERS 1-4 |
| OF THE NEC. HOWEVER IN ORDER TO CONSIDERED AN IT ROOM |
| BY DEFINITION, ALL CONSTRUCTION MUST MEET NFPA-75 AND |
| ALL ITEMS LISTED IN 645.4(1-5) MUST BE MET. BASED ON |
| THE PLANS SUBMITTED THIS LOCATION DOES NOT MEET THE |
| MINIMUM REQUIREMENTS TO BE CONSIDERED AN IT ROOM. |
| |
| ** IF THIS IS NOT GOING TO BE AN IT ROOM BY DEFINITION, |
| PLEASE ADJUST ROOM DESIGNATION AND PLEASE PLACE NOTE ON |
| ELECTRICAL PLANS WHICH STATES: *NO WIRING METHODS PER |
| NEC 645 PERMITTED*, OR WORDS TO THAT AFFECT. |
| PLEASE CALL TO GO OVER ANY QUESTIONS. |
| |
| 7) NOTE: PLEASE INDICATE ALL CIRCUITS ON PLANS AND |
| COORDINATE WITH PANEL SCHEDULES. BRANCH CIRCUIT LOADS, |
| WIRING ETC CAN NOT BE FULLY VERIFIED AT THIS TIME. |
| E 1.1 INDICATES THIS AS A CABLING PLAN. THERE IS NO |
| POWER PLAN AND POWER FOR RECEPTACLES IS ALL SHOWN ON |
| E1.1. PLEASE COMPLETE. |
| NEC 240.4, 310.16, 408.4, 210.19, 210.20, 210.21 ETC |
| PLEASE BE SURE TO SEE THE FOLLOWING FROM NEC 408.4 |
| WHICH DOES NOT PERMIT THE GENERAL DESCRIPTION AS |
| *RECEPTACLES* OR *LIGHTS*. ALL AREAS ARE REQUIRED TO BE |
| SPECIFIC TO THE ROOMS AND AREAS IN WHICH EACH BREAKER |
| FEEDS. EXAMPLE: LF-7, OFFICE 004 RECEPTACLES. THESE MAY |
| BE ALPHA OR NUMERIC DESIGNATIONS. |
| ** TEXT FROM CODE COMMENTARY IN THE NEC* |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 8) NOTE: PLEASE SEE 210.8B1-5 WHICH REQUIRES GFI |
| RECEPTACLES OR GFI PROTECTION. RECEPTACLES IN LOCATIONS |
| SUCH AS KITCHEN BREAK AREAS, BATHROOMS AND ALL |
| RECEPTACLES WITHIN 6FT OF OTHER SINKS ARE ALL REQUIRED. |
| |
| 9) NOTE: PLANS CONTAIN NOTES FOR FIRE ALARM HOWEVER |
| NONE SHOWN ON PLANS. EVEN THOUGH FIRE ALARM PERMITS ARE |
| SEPARATE ALONG WITH SEPARATE SHOP DRAWINGS, THE BASE |
| PLANS ARE ALL REQUIRED TO SHOW MINIMUM REQUIRED FOR |
| DESIGN INTENT. FS 633 |
| PLEASE SHOW ALL LOCATIONS, HEIGHTS AND MINIMUM LEVELS |
| FOR ADA COMPLIANCE. |
| PLEASE SEE FBC 11-4.28.1,.2 AND .3. |
| |
| 10) NOTE: PLEASE INCLUDE NOTES FOR WIRING PER NEC 517, |
| PART II. PER THE SCOPE OF WORK AND OCCUPANCY WIRING |
| SHALL CONTAIN REDUNDANT GROUNDING PER 517.13. |
| |
| 11) NOTE: RISER INDICATES TWO METERS AND TENANT |
| DISCONNECTS FOR ONE TENANT SPACE. NOTES ON PLANS STATE |
| THESE AS * SERVICES* HOWEVER PER NEC 100 THESE ARE NOT |
| SERVICES. PLEASE VERIFY WITH FIRE MARSHAL THAT MORE |
| THAN ONE DISCONNECTING MEANS WILL BE PERMITTED FOR ONE |
| TENANT SPACE. |
| |
| 12) NOTE: THE AIR CONDITIONING EQUIPMENT IS SHOWN ON |
| M-SHEETS HOWEVER NOT ON ELECTRICAL SHEETS. IN FACT |
| THERE ARE MORE BREAKERS FOR A/C EQUIPMENT IN PANEL HC |
| THAN SHOWN ON RISER. |
| IT IS UNCLEAR WHERE THE OTHER BRANCH CIRCUITS LISTED ON |
| PANEL HC IS? |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| |