Plan Review Notes For Permit 09120451 |
Permit Number |
09120451 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-13 11:07:02 | PLAN DENIED | | 1) PAGE 4 SHOWS A 7'' FLEX DUCT PENETRATING THE ONE | | HOUR STAIR ENCLOSURE . FLEXIBLE DUCT SHALL NOT PASS | | THROUGH ANY FIRE -RESISTANCE -RATED ASSEMBLY SECTION | | 607.7 FBC-M . | | 2) PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT | | INCLOSURE ARE PROHIBITED EXCEPT FOR EXIT DOORS IN | | ACCORDANCE WITH FBC-B 1020.1.2 . | | 3) PLEASE SHOW WHERE THE BATH EXHAUST TERMINATES ON THE | | PLANS SECTION 401.5 FBC-M . | | 4) SHOW TERMINATION OF CONDENSATE LINES ON PLANS . | | 5) PLEASE REFER TO SECTION 602.2.1METERIALS EXPOSED | | WITHIN PLENUM'S . | | 6) PROVIDE MANUFACTURER'S DATA FOR THE PTAC UNITS ON | | FIRST FLOOR SHOWING THE APPLIANCE ARE DESIGNED FOR WIND | | RESISTANCE SECTION 301.12 FBC-M .ALSO PROVIDE AN | | ENGINEERED WIND RESISTANT INSTALLATION DETAIL FOR THE | | PTAC SLEEVE AS WELL FOR THE ATTACHMENT OF THE UNIT | | WITHIN THE SLEEVE . | | 7) PLEASE BE ADVISED THAT THE ENERGY CALCULATIONS DO | | NOT MATCH THE PLANS . | | 8) PLEASE SHOW THE LOCATION AND THE SIZE OF THE RETURN | | AIR IN THE LIVING SPACE ON ALL THREE UNITS . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|