Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-01-11 15:45:48*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. SHOW THE LOCATION OF THE PORTABLE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 HAVE NOT LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
  
 6. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 SELF CLOSING AND SELF LATCHING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722