2009-12-28 12:35:06 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET 1 OF 4, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE LOAD CALCULATION INDICATES A 400 AMP SERVICE
 WITH 1/0 CONDUCTORS, THE RISER DIAGRAM INDICATES 350
 MCM (AND A 3/0???) BOTH OF WHICH DO NOT COMPLY WITH
 310.15 (B)(6) FOR CONDUCTOR SIZE. 400 MCM WOULD BE
 CORRECT FOR A 400 AMP SERVICE, AND NO GROUND WIRE IN
 THE RISER.ALSO SEE 250.94 FOR INTERSYSTEM BONDING.
  
 THE ELECTRICAL NOTE REGTARDING ARC FAULT BREAKERS IN
 THE BEDROOMS IS INCORRECCT, SEE 210.12 2008 NEC.
  
 3} THE PANEL LOCATION IN UNIT #3 IS IN VIOLATION OF
 240.24 (D), CLOTHES CLOSET.
  
 4} UNIT #1NEEDS A RECEPTACLE ADDED TO THE KITCHEN
 COUNTERTOP TO COMPLY WITH210.52 (C)(1) SPACING. SEE
 REVIEWED PLAN.
  
 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE
 ENTRANCE CONDUCTORS.
  
 6} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.