2009-12-29 16:37:26 | 2007 FBC W/2009 REVISIONS |
| LEVEL 3 ALTERATION |
| |
| DENIED BY BUILDING |
| |
| 1) THE PLANS ARE REQUIRED TO BE PREPARED, SIGNED, |
| SEALED AND DATED BY A FLORIDA LICENSED ARCHITECT OR |
| ENGINEER. FS 481.229 AND FS 471.003 |
| |
| 2) PER 405.1, THE WORK AREA EXCEEDS 50 PERCENT OF THE |
| AGGREGATE AREA OF THE BUILDING, WHICH MAKES THIS A |
| LEVEL 3 ALTERATION. PLEASE CORRECT. |
| |
| 3) IF THIS IS A 3-UNIT APARTMENT BUILDING, THE |
| OCCUPANCY TYPE IS R-2. PLEASE CORRECT. SEE FBC 310.1 |
| |
| 4) THE ENERGY CALCULATION FORM NEEDS TO BE SIGNED BY |
| THE OWNER AS WELL AS THE PREPARER. FBC 13-103.1.1.2.2 |
| REQUIRES THE FORM PREPARATION FOR MULTI-FAMILY |
| DWELLINGS TO BE SIGNED AND SEALED BY AN ARCHITECT OR |
| ENGINEER REGISTERED IN THE STATE OF FLORIDA. |
| |
| 5) PLEASE NOTE ON THE PLANS THAT THE EXISTING TENANT |
| SEPARATION WALLS, AS WELL AS, THE FLOOR/CEILING |
| SEPARATING TENANT SPACES ARE REQUIRED TO HAVE A ONE |
| HOUR FIRE RATING PER FBC 708.1 AND FBC 711.3. THE |
| BATHROOM LOCATED UNDER THE STAIRS IS REQUIRED TO HAVE |
| ONE HOUR FIRE SEPARATION FROM THE STAIRS LEADING TO THE |
| UNIT ABOVE. |
| |
| 6) SPECIFY THE WIND DESIGN INFORMATION INCLUDING WIND |
| SPEED, EXPOSURE CATEGORY, ETC. ON THE PLANS. SEE FBC |
| 1603.1.4. |
| |
| 7) SPECIFY THE REQUIRED COMPONENT AND CLADDING |
| PRESSURES FOR THE WINDOW AND DOOR OPENINGS ON THE |
| PLANS. SEE FBC 1604.9. THE ONES SPECIFIED ON THE PLANS |
| ARE NOT CORRECT. |
| |
| 8) PROVIDE THE UL LISTING OR FILE NUMBER FROM AN |
| APPROVED TESTING AGENCY FOR THE 1 HOUR FIRE RATED WALL |
| SYSTEM THAT WILL BE INSTALLED. SEE FBC 703. |
| |
| 9) PLEASE CLARIFY WHICH WINDOWS ARE TO BE REPLACED AND |
| WHICH OF THE EXISTING ONES WILL REMAIN. PLEASE NOTE |
| THAT A 37 X 50 WINDOW DOES NOT MEET EGRESS SIZE |
| REQUIREMENTS. SEE FBC 1026. |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE HORIZONTAL SLIDING |
| WINDOWS PER FAC RULE 9B-72, IF THEY ARE TO BE REPLACED. |
| |
| 11) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE PROJECT. FBC 106.3.3 CITY AMENDMENTS. |
| |
| 12) THE ROOM HOUSING THE DRYER FOR UNIT # 2 THAT |
| LOCATED UNDER THE EGRESS STAIRS FOR UNIT #3 IS REQUIRED |
| TO HAVE 1 ONE FIRE RATED WALLS AND CEILING THAT |
| SEPARATE IT FROM THE STAIRS AND LANDING OF THE ADJACENT |
| TENANT SPACE. FBC 708 AND 711. |
| |
| 13) SPECIFY DRAFTSTOPPING IN THE COMBUSTIBLE FLOOR |
| CONSTRUCTION ABOVE AND IN LINE WITH THE DWELLING UNIT |
| SEPARATIONS ON THE PLANS. SEE FBC 717.3. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |