Plan Review Notes
Plan Review Notes For Permit 09120422
Permit Number 09120422
Review Stop B
Sequence Number 1
Notes
Date Text
2010-01-04 12:02:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHOW COMPLIANCE WITH FBC TABLE 503 AND FBC TABLE
 602. A SITE PLAN SHOULD BE PROVIDED WHICH SHOWS
 DISTANCE BETWEEN BUILDINGS, DISTANCE FROM PROPOSED NEW
 BUILDING TO THE PROPERTY LINE, BUILDING TYPE (FBC CH 6)
 AND OCCUPANCY CLASSIFICATION (FBC CH 3). MORE
 INFORMATION MAY BE REQUIRED. ENOUGH INFORMATION SHOULD
 BE PROVIDED TO SHOW COMPLIANCE WITH FBC TABLE 503 AND
 FBC TABLE 602.
  
 2. PROVIDE INFORMATION REGARDING THE PROPOSED NEW
 RELOCATED BUILDING. FOR THE BUILDING TO BE RELOCATED,
 PROVIDE EITHER A COPY OF THE ORIGINAL PERMIT PLANS, A
 COPY OF THE DCA APPROVED PLAN, OR A SIGNED AND SEALED
 SET OF AS-BUILT PLANS. YOU MAY FIND THE DCA WEBSITE
 HELPFUL:
  
 HTTP://WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q
 &A-0108_V3.PDF
  
 3. DECLARE OCCUPANCY CLASSIFICATION FOR THIS STRUCTURE
 AND EITHER REVISE THE PLANS TO SHOW COMPLIANCE WITH FBC
 CHAPTER 11 OR INCORPORATE EXCEPTION INTO THE PLAN. SEE
 OTHER COMMENTS.
  
 4. THE PLAN SHOWS THE STRUCTURE AT 1'4" ABOVE GRADE.
 DOES THE STRUCTURE INCLUDE STAIRS FOR ACCESS AS A PART
 OF THE DCA APPROVAL, OR IS THIS TO BE SITE BUILT? SEE
 FBC CHAPTER 10. PROVIDE DETAILS AS REQUIRED.
  
 5. NOT ENOUGH INFORMATION WAS PROVIDED TO DETERMINE
 CODE COMPLIANCE. THE PLANS STATE THAT AN "EXISTING
 WOODY WASTE TRAILER" IS TO BE REPLACED, BUT BASED ON
 THE FLOOR PLAN IT APPEARS THAT THE NEW TRAILER CONTAINS
 OFFICES OR WORK AREAS.
  