2010-01-04 12:02:12 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. SHOW COMPLIANCE WITH FBC TABLE 503 AND FBC TABLE |
| 602. A SITE PLAN SHOULD BE PROVIDED WHICH SHOWS |
| DISTANCE BETWEEN BUILDINGS, DISTANCE FROM PROPOSED NEW |
| BUILDING TO THE PROPERTY LINE, BUILDING TYPE (FBC CH 6) |
| AND OCCUPANCY CLASSIFICATION (FBC CH 3). MORE |
| INFORMATION MAY BE REQUIRED. ENOUGH INFORMATION SHOULD |
| BE PROVIDED TO SHOW COMPLIANCE WITH FBC TABLE 503 AND |
| FBC TABLE 602. |
| |
| 2. PROVIDE INFORMATION REGARDING THE PROPOSED NEW |
| RELOCATED BUILDING. FOR THE BUILDING TO BE RELOCATED, |
| PROVIDE EITHER A COPY OF THE ORIGINAL PERMIT PLANS, A |
| COPY OF THE DCA APPROVED PLAN, OR A SIGNED AND SEALED |
| SET OF AS-BUILT PLANS. YOU MAY FIND THE DCA WEBSITE |
| HELPFUL: |
| |
| HTTP://WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q |
| &A-0108_V3.PDF |
| |
| 3. DECLARE OCCUPANCY CLASSIFICATION FOR THIS STRUCTURE |
| AND EITHER REVISE THE PLANS TO SHOW COMPLIANCE WITH FBC |
| CHAPTER 11 OR INCORPORATE EXCEPTION INTO THE PLAN. SEE |
| OTHER COMMENTS. |
| |
| 4. THE PLAN SHOWS THE STRUCTURE AT 1'4" ABOVE GRADE. |
| DOES THE STRUCTURE INCLUDE STAIRS FOR ACCESS AS A PART |
| OF THE DCA APPROVAL, OR IS THIS TO BE SITE BUILT? SEE |
| FBC CHAPTER 10. PROVIDE DETAILS AS REQUIRED. |
| |
| 5. NOT ENOUGH INFORMATION WAS PROVIDED TO DETERMINE |
| CODE COMPLIANCE. THE PLANS STATE THAT AN "EXISTING |
| WOODY WASTE TRAILER" IS TO BE REPLACED, BUT BASED ON |
| THE FLOOR PLAN IT APPEARS THAT THE NEW TRAILER CONTAINS |
| OFFICES OR WORK AREAS. |
| |