2010-05-06 16:58:17BUILDING PLAN REVIEW
 PERMIT: 09120421
 ADD: 105 NARCISSUS ST.
 CONT: L B DEVELOPMENET & ENGINEERING
 TEL: (954)709-1926
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 MAY 10TH/ 2010
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2007 FBC EXISTING BUILDING CODE 701.3 ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2)SECOND REQUEST, THIS BUILDING WILL NEED TO MEET THE
 REQUIREMENTS OF 1406.2.2 ARCHITECTURAL TRIM WHEN IT
 EXCEEDS 40 FEET ABOVE GRADE, (NON-COMBUSTIBLE MATERIAL
 AND SECURED TO WALL WITH METAL OR OTHER APPROVED
 NONCOMBUSTIBLE BRACKETS). PLEASE PROVIDE THE
 MANUFACTURES SPECS FOR EACH TYPE (EDON MOLDINGS & FYPON
 BRACKETS) OF ARCHITECTURAL TRIM TO BE INSTALLED.
 703.4 NON-COMBUSTIBILITY
 703.4.1 ELEMENTARY MATERIALS.
 703.4.2 COMPOSITE MATERIALS.
 IF THE DESIGNER SWITCHES TO MCM PANELS FOR
 ARCHITECTURAL TRIM SECTION 1407.3
  
 2A) PRODUCT SUBMITTALS:
 MIAMI-DADE NOA 07-0618.05
 AGGRE-FLEX CLASS PB EXTERIOR INSULATION AND FINISH
 SYSTEM THIS IS A EFIS WALL SYSTEM NOT A TRIM APPLIED TO
 THE EXTERIOR OF THE BUILDING. THIS NOA DOES NOT HAVE
 ANY INFORMATION INDICATING
 THAT IT MEETS THE TEST OF NON-COMBUSTIBILITY AS
 REQUIRED BY 1407.3.
 2603.5 EXTERIOR WALLS OF BUILDINGS OF ANY HEIGHT.
 EXTERIOR WALLS OF BUILDINGS OF TYPE I, II, III OR IV
 CONSTRUCTION OF ANY HEIGHT SHALL COMPLY WITH SECTIONS
 2603.5.1 THROUGH 2603.5.7
 2603.5.4 FLAME SPREAD AND SMOKE-DEVELOPED INDEXES. FOAM
 PLASTIC INSULATION, EXTERIOR COATINGS AND FACINGS SHALL
 BE TESTED SEPARATELY IN THE THICKNESS INTENDED FOR USE,
 BUT NOT TO EXCEED 4 INCHES (102 MM), AND SHALL EACH
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF 450 OR LESS AS DETERMINED IN
 ACCORDANCE WITH ASTM E 84.
  
 2B) FUTURA STYROTHANE 5321 FR AROMATIC URETHANE &
 STROTHANE A100 BOTH INDICATE WITHIN THEIR MSDS SHEETS :
 FLAMMABLE PROPERTIES: COMBUSTIBLE, CLASS III-B
  
 3) 2ND REVIEW THIS COMMENT WILL NOT BE RELAVENT TO FOAM
 TYPE TRIM.
 PLEASE ALSO REVIEW SECTION 1406.2.4 FIRE BLOCKING AND
 717.2.6 ARCHITECTURAL TRIM AND FIRE BLOCKING
 REQUIREMENTS.
  
 4 )2ND REVIEW. SHEET 2 & 4 BOTH INDICATE NEW BALCONIES
 AND GUARD RAILS PLEASE REVIEW 1406.3 FBC- BUILDING AND
 CODE COMMENTARY. BALCONIES AND SIMILAR APPENDAGES IN
 BUILDINGS OF TYPE I AND II CONSTRUCTION ARE REQUIRED TO
 BE CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS IN ORDER TO
 PREVENT FIRE INVOLVEMENT AND THE SPREAD UP OR ALONG THE
 EXTERIOR OF A NON-COMBUSTIBLE BUILDING.
  
 5)2ND REVIEW. SHEET 4 DETAILS INDICATE THIS BUILDINGS
 EXTERIOR WALLS ARE CONSTRUCTED OF 8 INCH CMU OR
 CONCRETE BLOCKS. PLEASE FIELD VERIFY THAT THIS IS A
 TRUE STATEMENT. AT THE TIME THIS BUILDING WAS
 CONSTRUCTED, (1925) IT WAS COMMON TO USE STRUCTURAL
 TERRA COTTA TILE IN THE EXTERIOR WALL CONSTRUCTION.
 THIS TILE IS VERY THIN, BRITTLE AND DRILLING INTO THE
 BLOCKS TO ANCHOR ANOTHER MATERIAL CAN BE DIFFICULT. IT
 OFTEN RESULTS IN A BLOW-OUT OF AN AREA OF MUCH LARGER
 DIAMETER THAN THE INTENDED HOLE!
  
 **INFORMATIONAL**: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved