2010-01-05 11:10:56 | COMMENTS: |
| |
| #1 PROVIDE A PLAN TO SCALE SHOWING DRIVEWAY ENTRANCE |
| APPROACH WIDTH AND ALSO EXIT WIDTH. |
| #2 PROVIDE PERVIOUS AND IMPERVIOUS CALCULATIONS. |
| #3 WATER RUNOFF SHALL BE DISCHARGED FROM IMPERVIOUS |
| SURFACES THROUGH RETENTION AREAS, DETENTION DEVICES, |
| FILTERING AND CLEANSING DEVICES, OR SUBJECT TO SOME |
| OTHER TYPE OF BEST MANAGEMENT PRACTICE (BMP) PRIOR TO |
| DISCHARGE FROM THE SITE. PROVIDE STORMWATER CALCULATION |
| AND PROPOSED EXFILTRATION. PLAN MUST REFLECT SUCH |
| INSTALLATION. |
| #4 DUMPSTER LOCATION IS NOT SHOWN |
| #5 WATER SERVICE MUST BE SIZED ACCORDINGLY TO IRRIGATE |
| LANDSCAPING. A SEPARATE IRRIGATION METER IS RECOMMENDED |
| SO THAT SEWER FEES AREN'T PAID AGAINST DOMESTIC WATER |
| USE. |
| #6 DRIVEWAY APRON MUST MEET ENGINEERING SERVICES |
| CRITERIA. |
| #7 OFF-SITE PARKING NEEDS TO BE STRIPED TO AVOID |
| CONFLICT WITH ALLEYWAY AND ENTRANCE VISIBILITY. |
| COORDINATION WITH ROW DEPT. WILL BE REQUIRED. |
| WINDEL G PALMER UTILITIES ENGINEERING PROJECT |
| COORDINATOR CITY OF WPB RIGHT OF WAY 401 CLEMATIS |
| STREET WEST PALM BEACH, FL 33401 PHONE: 494-1040 EXT: |
| 1086 |
| FAX: 494-1069 E-MAIL: [email protected] |
| HTTP://WWW.CITYOFWPB.COM/ENGINEERING/UPLOADS/2009-06-04 |
| -14-16-04-CWPBRIGHT-OF-WAYPERMITPACKAGE.PDF |
| |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |