Notes |
Date |
Text |
2010-02-25 08:25:00 | REVISION DENIED | | | | REVISED CALCULATIONS DO NOT SPECIFY THE TDH. THE | | MAXIMUM CAPACITY OF THE PUMP ( 100 GPM) WAS USED. THE | | MAIN DRAINS HAVE 2" OUTLETS WHICH ARE PART OF THE | | BRANCH PIPING. ANSI/APSA-7 2006 SECTION 4.4 LIMITS | | WATER VELOCITY TO A MAXIMUM OF 6 FPS. THE FLOW RATE | | THROUGH 2" PIPE AT 100 GPM EXCEEDS 6 FPS. PLEASE | | CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|