Plan Review Notes For Permit 09120397
Permit Number 09120397
Review Stop P
Sequence Number 2
Notes
Date Text
2010-02-25 08:25:00REVISION DENIED
  
 REVISED CALCULATIONS DO NOT SPECIFY THE TDH. THE
 MAXIMUM CAPACITY OF THE PUMP ( 100 GPM) WAS USED. THE
 MAIN DRAINS HAVE 2" OUTLETS WHICH ARE PART OF THE
 BRANCH PIPING. ANSI/APSA-7 2006 SECTION 4.4 LIMITS
 WATER VELOCITY TO A MAXIMUM OF 6 FPS. THE FLOW RATE
 THROUGH 2" PIPE AT 100 GPM EXCEEDS 6 FPS. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]